Instructions / Assembly
• Vent system must  terminate to the  outside
(roof or side wall).
• DO NOT terminate the vent system in an at- 
tic or other enclosed area.
• DO NOT use 4” (10.2 cm) laundry-type wall
caps.
• Use metal/aluminum vent only. Rigid metal/
aluminum vent is recommended.
• DO NOT use plastic vent.
• Always keep the duct clean to ensure proper
airflow.
• Calculate the following figures before instal- 
lation:
Maximum ceiling clearance 
110”  at  30”  hood  mounting 
height  above  countertop/ 
stove (may vary with differ- 
ent model). 
Chimney- 
mounting 
Bracket 
Upper 
Chimney 
Lower 
Chimney 
Range hood
1. Distance from the floor to the ceiling.
2. Distance between the floor to the coun- 
tertop/stove
3. Distance  between  the cooking surface
to the range hood (recommend 24” to
30”) minimum of 30” is required for
gas stove top
4. Height of hood and duct cover.
For the most efficient & quiet operation: 
• A  distance  of  24”  to  30”  is  recommended
between  stove  top  and  the  bottom  of  range
hood. 30” minimum is required for gas stove
tops.
• It  is  recommended  that  the  range  hood  be
vented vertically through the roof through 6”
(15.3 cm) or bigger round metal/aluminum
vent work.
• The size of the vent should be uniform.
• Use no more than three 90° elbows.
• Make  sure  there  is  a  minimum  of  24”  (61
cm) of  straight  vent between the elbows if
more than one elbow is used.
• DO NOT install two elbows together.
• The  length  of vent  system  and  number  of
elbows should be kept to a minimum to pro- 
vide efficient performance.
• The  vent system must  have  a  damper. If
roof  or wall  cap  has  a damper,  DO NOT
use damper (if supplied) on top of the range
hood.
• Use silver tape or duct tape to seal all joints
in the vent system.
• Use caulking  to seal  exterior  wall or  roof
opening around the cap.
Max: 110” 
Min: 24” 
Max: 30” 
36” base 
Countertop/Stove 
5
Venting Requirements:
Height & Clearance: