User manual

Configuration
13 © 2007-2014 Analytica GmbH
To start the execution of a script click on the button Start.
Via button Delete a script can be deleted on the device and
via Boot a script can be defined as boot script.
script output area In this text area the standard output (stdout) of the currently
executing script is displayed. Via the button Clear this text
area can be cleared.
error output area In this text area the standard error output (stderr) of the
currently executing script is displayed. Via the button Clear
this text area can be cleared.
Tip
The text areas for script and error output are not refreshed automatically.
A manual page reload of the current page refreshes both text areas.
2.7. Digital IO
2.7.1. Pin layout of plug
Over the 10-pole pin row on the back of the AnaGate CAN Gateway four digital inputs
and four digital outputs are led out, which can be used freely. Since the IO's are
electrically isolated from the device, they must be separately supplied via the pins
1 us 2 with a voltage by 3,3V - 24V DC.
Figure 2.7. Pin layout, digital IO plug
2.7.1.1. Connecting the digital inputs
At the inputs IN1 to IN4 any external voltage between VCC and GND can be applied.
As soon as the voltage difference between INx and GND is more than 1.0 V, the
AnaGate CAN Gateway interprets the input as logically HI otherwise LOW.
2.7.1.2. Connecting the digital outputs
The outputs are implemented as open collector drivers. If a output is active, it is
pulled down to GND. In the inactive condition the output is floating.
In principle the maximum current of each individual output is 400mA. For thermal
reasons is the sum of all output currents is limited to 500mA. The outputs not short-
circuit proofed, and must be protected with a pre-resistor.