Specifications

4
LOAD SHARE OPTION
The units may be configured for load sharing if they are equiped with the optional output isolation
diodes. To confirm that your unit has these diodes, use an ohmmeter to measure the resistance
between the two positive output terminals. If the diodes are present the terminals will measure as not
connected. If the diodes are NOT present, the terminals will measure as a short circuit. Assuming
the output isolation diodes are present, connect one 4 foot piece of red wire of the appropriate gauge
(as shown in the table below)
to each positive output terminal. Connect all the positive wires to a distribution bus, or connect them
together, and then connect from the common point to the load using the correct gauge of wire for the
total output capability of all the supplies running in parallel. Repeat this process for the negative
terminals using the same gauges of wire, but black in colour. These units should now load share.
You can confirm this by watching the output ammeters. A slight difference is negligable, however, if
this is not the case, you can increase the output voltage of the unit that is reading low using the
output adjust potentiometer.
Output Voltage (Vdc) 12 24 48
Wire Gauge (AWG) #8 #12 #14