IPSi365 Series Manual
98
This unit is also equipped with a NEMA 5-15 AC outlet as a secondary AC Output Connection. 
This outlet is identical to a North American AC Mains outlet. This unit can also be constructed 
with a European AC or Worldwide AC mains compatible outlets by custom order.
CAUTION: DO NOT APPLY AC VOLTAGE TO 
ANY AC OUTPUT CONNECTION. 
This will damage the inverter and will not be 
covered under warranty.
DC Input Connections
AC Output Connections
DC INPUT POWER CONNECTION
This unit is equipped with a pair of color-coded Phoenix VDFK6 terminal block connectors to 
serve as a DC Input Connection. 
Connect the DC input power here using AWG8/10mm
2
 wire. The wires should be stripped 
0.4 inches/9mm and tightened securely to 16 inch-pounds/1.8 Newton Meters. The terminal 
blocks are color-coded to indicate polarity which is as follows: 
AC OUTPUT CONNECTION
This unit is equipped with three color-coded Phoenix VDFK4 terminal block connectors to serve 
as a hard wired AC Output Connection.
Connect the AC load here using wires from AWG24/0.25mm
2
 to AWG10/ 6mm
2.
 The wires 
should be stripped 0.3 inches/ 8mm and tightened securely to 16 inch-pounds/1.8 Newton 
Meters. The terminal blocks are color-coded to indicate polarity which is as follows: 
NA 220VAC 60HZ
 - part code“U”-
WW 220VAC 50HZ
 - part code“W”-
Connector Color Polarity
Black AC Hot/Live
Gray AC Neutral
Green/Yellow AC Ground (Chassis)
Connector Color Polarity
Red DC Input Positive
Black DC Input Negative
CAUTION: DO NOT REVERSE CONNECT THE DC INPUT POWER