IPSi305W_Manual
1312
Specications
Input -12 -20 -40
Nominal Voltage 12 VDC 24, 28, 32, or 36 VDC 48 or 72 (Rail) VDC
Actual Voltage 10.5-18 VDC 19 - 48 VDC 39 - 84 VDC
Input Amps (Max.) 49 A 24 A 12 A
Input Fuse (Internal)
2x 30A 32 VDC Blade 
Mini
1x 30A 58 VDC Blade Mini 1x MDA - 15A fuse
Under Voltage Input 
Alarm 
Shutdown Range
10.5-14 VDC
(Default setting: 10.5 
VDC)
19-36 VDC
(Default setting: 21 VDC)
39-70 VDC
(Default setting: 42 VDC)
Under Voltage Input 
Alarm 
Start-up Range
11-14 VDC
(Default setting: 11VDC)
20-36 VDC
(Default setting: 23VDC)
40-70 VDC
(Default setting: 10.5 VDC)
Under Volt Input 
Shutdown Delay
1-120 seconds (Default setting: 30 seconds)
Over Voltage 
Input Shutdown
19 VDC 49 VDC 86 VDC
Inrush Current (From 
fully discharged)
1.8 Amp Peak 4.8 Amp Peak 8.4 Amp Peak
Output -110
Nominal Voltage 110 VAC
-220
220 VAC
Continuous Amps 2.5 A  1.3 A 
Peak Amps 3 A 1.5 A
Output Frequency 50.00 or 60.00 Hz ± 0.1 Hz (User-selectable)
Output Distortion (THD) <2% at 360 VA into resistive load
Regulation 
(Line & Load)
< +/- 2.0%
Duty Cycle  100% for 24 hours per day / 1 min @ peak with 10 minute cool down
Efciency 85% @ Full load
Ground Fault Trip 
Current
4-6 mA