IPSi305W_Manual

1110
InverterWizard (Optional)
InverterWizard is optional software that can be used to adjust the inverter’s operating
settings. InverterWizard is free-to-download from www.analyticsystems.com or available by
emailing sales@analyticsystems.com
Using InverterWizard, you can:
Set the inverter’s output frequency to either 50.00 or 60.00 Hz.
Adjust the inverter’s output voltage over a ±10% range in 1 VAC intervals.
Set the voltage thresholds for the low voltage alarms.
Set the voltage thresholds for UPS function to start and stop.This function is only
available on units with the UPS option. See Off-line UPS for more information.
Update the inverter’s rmware.
Monitor and record the inverter’s operating data.
ALTERNATE DC VOLTAGES AND LOW VOLTAGE SHUTDOWN
IPSi series Intelligent inverters are factory-preset for the low voltage alarm/shutdown to
trigger if the unit detects an input voltage drop of:
<12 VDC for a -12 model
<24 VDC for a -20 model
<48 VDC for a -40 model
If the inverter uses an alternate input voltage such as 32 VDC, 36 VDC, or 72 VDC (rail) battery
then the low voltage shutdown thresholds will need to be adjusted using InverterWizard.
NOTE: INVERTERWIZARD IS NOT REQUIRED TO OPERATE THE INVERTER.
The inverter can immediately be put into service if its default operating settings are suitable
for your needs. The inverter’s default settings are listed its label.