There are 8 LED indicators labelled 1 through 8. Their functions are as follows: 
1.  Low Input Voltage: Blinks Red when the input voltage is near the lower limit for proper 
operation. Glows Red when the input voltage is too low for proper operation and will be 
accompanied by the Bypass LED glowing Red and the On/Off switch will not be glowing. 
Check for the reason for low voltage.
2.  High Input Voltage: Blinks Red when the input voltage is near the upper limit for proper 
operation. Glows Red when the input voltage is too high for proper operation and will be 
accompanied by the Bypass LED glowing Red and the On/Off switch not glowing. Check 
for the reason for high voltage. The inverter can be damaged if the input voltage exceeds 
the maximum rating, and excess voltage damage is not covered under warranty.
3.  Over Temp: Blinks Red if the internal temperature of the inverter is approaching the safe 
limit. The inverter will reduce its maximum power rating to try to maintain the tempera-
ture within safe limits. The LED will glow Red if the inverter is too hot to operate and 
the Bypass LED will also glow Red and the On/Off switch will stop glowing. Either the 
cooling fan is defective, or there is not enough air circulation for the inverter. If the fan is 
running, add extra ventilation. If the fan is NOT running the inverter must be returned for 
repair.
4.  Overload: Blinks Red if the load on the inverter reaches the continuous rating. Solid Red 
if the load on the inverter reaches the maximum rating. Reduce the load on the inverter.
5.  50 Hz: This LED will be on Green if the inverter is set for 50 Hz operation. 
6.  60 Hz: This LED will be on Green if the inverter is set for 60 Hz operation.
7.  Bypass: This LED will be on Green if the inverter is in Bypass mode, or on Red if the 
inverter is in an Alarm condition as described above.
8.  Invert: This LED will be on Green when the inverter is in normal operation.