Product Datasheet
ENVIRONMENTAL AND SAFETY
Operating Temperature Range
-25°C to +40°C @ maximum output. Derate Linearly 2.5% per °C from 40°C
(Optional -40°C wide temperature range available)
Humidity
0 - 95% Relative Humidity
(non-condensing) with standard conformal coating
Audible Noise Fan Speed Dependent (34.5 dB @ 3ft @ max fan speed)
Isolation Input-Case, Input-Output and Output-Case 1500 VDC
Warranty Three years parts and labor
Safety Built to CSA 22.2.107.1 & UL458 standards
INPUT
Nominal (ip) 12 VDC 24, 28, 32 or 36 VDC 48 or 72 VDC
Actual (VDC) 11 - 15 20 - 50 40 - 90
Input Fuse
(external user supplied)
120 60 30
OUTPUT
Output Nominal (op) 110 220
Output Volts (AC) 110 ± 10 VAC (user adjustable) 220 ± 20 VAC (user adjustable)
Output Amps 10 A (cont) / 12 A (peak) 5 A (cont) / 6 A (peak)
Output Frequency 50.00 or 60.00 Hz ± 0.01 Hz (user selectable)
Output Distortion < 2% at 1200 Watts into resistive load
Regulation (Line & Load) < +/- 2.0%
Duty Cycle Continuous 100% for 24 hours per day
Efciency > 90% @ Maximum Output
MECHANICAL
Dimensions
13.4 in +/- 0.1 in / 33.9 cm +/- 0.3 cm Long
9.4 in +/- 0.1 in / 23.8 cm +/- 0.3 cm Wide (including mounting anges)
7.7 in +/- 0.1 in / 19.6 cm +/- 0.3 cm High
Clearance 1.0 in / 2.5 cm all around
Weight 30 lb / 13.6 kg
Material and
Finish
Marine Grade Black Anodized Aluminum with 18-8 Stainless Fasteners
Mounting Shelf Mount
Connections
DC In – Marathon ST722B2502UH, 175 Amp, 300V Rating c/w Protective Snap On Cover
AC Out – 1 x NEMA 5-15 receptacle or 1 x 16A 250V CEE 7/7 receptacle with circuit
breaker protection, plus one 30A hardwire connection
AC In – one 30A hardwire connection (with Off-Line UPS Option)
8.00
12.30
7.73
2.15
7.95
9.38
OPTIONS
AC Detect and Auto-switch
(Off-line UPS)
COTS - MIL-STD-461F and
MIL-STD-810G In-house test & report
MIL-STD-461F
Stand alone test & report
MIL-STD-810G
Stand alone test & report
European ROHS compliant
(Lead Free Manufactured)
Military Rugged Package
with MIL Connectors
Safety Special Inspection (CSA/UL)
Integrated Digital Volt/Ammeter
IP66 or IP67 Water Resistant Chassis
Heavy duty ruggedization with wide
temperature range
DIMENSIONS
AnalyticSystems.com
sales@analyticsystems.com
604.946.9981 800.668.3884
8128 River Way
Delta BC V4G 1K5
IPSi1200 | INTELLIGENT PURESINE INVERTER