12 13
InverterWizard Program
The Inverter is factory preset for the input voltage, output voltage, and output frequency on the
label. If these parameters are satisfactory, the Inverter can be put immediately into service.
The low voltage shutdown parameters are set for the lowest battery voltage that the Inverter
will support. They are:
12 Volts for a -12 model
24 Volts for a -20 model
48 Volts for a -40 model
If the Inverter is powered by alternate DC battery voltage such as 32/36 Volts for a -20 model
or 72 Volts (rail) for a -40 model, then the low voltage shutdown parameters will need to be
changed. You can do this using the free-to-download InverterWizard software from
www.analyticsystems.com
With InverterWizard, you can also:
Set the Output Frequency (50.00 or 60.00 Hz)
Adjust the Output Voltage (±10% range at 1 VAC intervals)
Set the voltage thresholds for UPS (For units with the Off-line UPS Option)
Update the Inverter’s rmware version
Monitor and record the Inverter’s operating data