Product Datasheet
ENVIRONMENTAL AND SAFETY
Operating Temperature Range -25°C to +40°C @ Continuous Output
Isolation Input-Output, Output-Case, and Input-Case: 1500 VDC
Input Connections
DC Input: Red and Black Phoenix VDFK 4 Feed Through
Connectors
AC Input: Green, Gray, and Black Phoenix VDFK 4 Feed
Through Connectors (Off-line UPS Option)
Output Connections
AC Output (1): Green, Gray, and Black Phoenix VDFK 4 Feed
Through Connectors
AC Output (2): NEMA 5-15 Receptacle
Audible Noise 34.5 dB @ 3 feet / 1 meter
Warranty 3 Years Parts and Labor
INPUT -125
Nominal Voltage 125 VDC
Actual Voltage 100-140 VDC
Input Amps (max) 16 A
Input Fuse External fuse required, not supplied
OUTPUT -110V -220V
Nominal Voltage 110 ± 2 VAC 220 ± 4 VAC
Output Voltage Adjust Range ± 10 VAC ± 20 VAC
Output Amps (max) 10A (cont.) / 12A (peak) 5A (cont.) / 6A (peak)
Output Frequency 50.00 or 60.00 Hz ± 0.01 Hz (user selectable)
Output Distortion < 2% at 1200 Watts into resistive load
Regulation (Line & Load) < +/- 2.0%
Duty Cycle Continuous: 100% for 24 hours per day / Peak: 10% for 1 minute
Efciency > 90% @ Maximum Output
Transfer Time < 19 milliseconds (Off-line UPS Option)
MECHANICAL
Length 12.3 in / 31.2 cm
Width 9.4 in / 23.9 cm (including lifting handles)
Height 7.8 in / 19.8 cm
Clearance 1.0 in / 2.5 cm (all around)
Weight 30.0 lb / 13.6 kg (estimated)
Material and Finish Black Anodized Marine Grade Aluminum
Fastenings 18-8 Stainless Steel
OPTIONS
Ofine UPS Functionality
COTS - MIL461F and MIL810G in-house
testing with report for each unit
Heavy-duty Ruggedization
Safety Special Inspection (CSA/UL)
DIMENSIONS
IPSi1200-125 | INTELLIGENT PURESINE INVERTER
AnalyticSystems.com
Sales@AnalyticSystems.com
604.946.9981 800.668.3884
8128 River Way
Delta, B.C. V4G 1K5
Worldwide 220V Outlet
(220W Option)
North America 220V Outlet
(220N Option)
Hard Wired Connection
(Can be combined with
any outlet)
ALTERNATIVE 220V OUTLETS