Product Manual

8
Connection
AC
POL
TEMP
25
DEV
CH
75
SVC
FLT
LO V
BAT
50
EQ
PS
INSTALLATION INDICATORS
AC PRESENT BATTERY POLARITY REVERSED
AC
POL
TEMP
25
DEV
CH
75
SVC
FLT
LO V
BAT
50
EQ
PS
1. Connect the charger to the batteries before connecting to the AC mains.
2. As you complete the connection to each battery, check the ‘REV’ indicator light on the
charger front panel. If it glows RED, the battery is connected in reverse. Stop and reverse
the connections to the battery (Red should go to Positive and Black should go to Nega-
tive). After all battery banks are connected, double check that the REV indicator light is
still OFF.
3. Connect the charger to the AC mains. The AC LED should illuminate. This indicates that
the charger is receiving power from the AC mains and that the internal power supply is
running. Turn the charger OFF again.
Press the Power button on the front panel to turn the
charger ON. The Power button will illuminate once
the charger has turned on. Once the startup routine is
complete, enter Setup mode by pressing and holding
the PRG button for 3 seconds until you hear a one
second beep and the Charge LED starts blinking
Setup
Battery Type
Each press of the Equalize (EQU) button will advance the battery selection. The three LED’s on
the top will indicate Flooded, AGM and Gel when lit. The fourth press will light all three LED’s
if there is a valid custom conguration.
Flooded – The lead–acid battery was invented in 1859 by French physicist Gaston Planté and
is the oldest type of rechargeable battery. Despite having a very low energy-to-weight ratio
and a low energy-to-volume ratio, its ability to supply high surge currents means that the cells
have a relatively large power-to-weight ratio. These features, along with their low cost, make