Product Manual
5
Specications
Input
Volts 85 - 265VAC, 1 Phase, 45 - 65 Hz
Current (max) * 4 Amps w/ Inrush Protection
Input Fuse AGC 5 Amp
Power Factor >0.99 at Full Load
Efciency >90% at Full Load
* Maximum Input Current Specied at 85 VAC
Output
Nominal Voltage 12 VDC 24 VDC 36 VDC 48 VDC
Voltage Range ** 12.0 - 15.5 VDC 24.0 - 31.0 VDC 36.0 - 46.5 VDC 48.0 - 62.0 VDC
Output Current 20 Amps 10 Amps 6.8 Amps 5 Amps
Recommended Battery Amp-Hours 100 50 37 25
Standard Temperature Compensation -15mV/C -30mV/C -45mV/C -60mV/C
Charging Stages 2 or 3 stage user selectable
End of Charge Float or Rest user selectable
** Actual Output Voltage determined by User Settings or by Charger Firmware
Mechanical
Dimensions 9.5"/24.1cm Long x 8.0"/20.3cm Wide x 3.25"/8.3cm High
Clearance 1.0"/2.5cm all around
Weight 6.2 lb / 2.8 kg
Material and Finish Marine Grade Black Anodized Aluminum with 18-8 Stainless Fasteners
Mounting Wall or Shelf Mount
Connections Integrated Color Coded Terminal Blocks
Environmental and Safety
Operating Temperature Range -25 to +40 C (-40 to +55 C Optional)
Storage Temperature Range -55 to +85 C
Humidity 0 - 95% Relative Humidity (non-condensing)
Vibration Built to meet MIL810g
Emissions Built to meet MIL461f
Isolation > 1500 VDC Input-Output, Input-Case, Output-Case
Audible Noise None
Duty Cycle Continuous
Warranty Ten Years Parts and Labor
Safety Built to meet ABS, CE, UL458 and CSA 22.2.107.1
* Specications subjects to change without notice.
Designed and manufactured by: ANALYTIC SYSTEMS WARE (1993) LTD.
8128 River Way
Delta, BC V4G 1K5 Canada
p. 604.946.9981 f. 604.946.9983
tf. 800.668.3884 US/Canada
www.analyticsystems.com analyticinfo@analyticsystems.com Revised July 2014