Remote Control Option
A remote control panel may be connected to the battery charger using a 9-pin D-connector 
that attaches to the side of the battery charger. The remote control panel and D connector 
are part of the remote control option. The remote control panel allows the unit to be operated 
remotely as well as duplicating all the diagnostic indicators and audible alarm.
REMOTE CONNECTOR
This connector is located on the side of the unit. Important: To prevent the possibility of High 
Voltage Electrical Shock, do not power up the battery charger unless all wiring from the unit to 
the remote is securely connected. Do not remove the dust cover from the DB-9 connector if the 
remote is not being used.
IMPORTANT: This remote is to be used 
only on Battery Chargers manufactured by 
Analytic Systems.t
Equalize Option
The purpose of the Equalize Option is to deliberately overcharge the battery at a low rate of 
current to ensure that all cells are fully charged and to reduce the chance of sulfation of the 
battery. During the Equalize cycle, the cells, which are fully charged, will produce Hydrogen 
gas, and the cells, which are undercharged, will be brought up to full charge. An Equalize 
cycle should be done once every 2-3 months, or whenever battery capacity appears to be 
diminished. The Equalize Option also includes a battery temperature sensor to compensate the 
charging voltage for battery temperature, as well as to shut the charger down if the battery 
should become overheated. A 2nd temperature sensor can be added to allow monitoring of 
both batteries if the charger is connected to 2 banks of batteries. 
An Equalize cycle can be initiated at any time by simply pressing the equalize start button 
located next to the ON/OFF switch. This button is deliberately recessed to prevent accidental 
operation. It is most easily pressed by using a ballpoint pen. If the charger is in the middle 
of charging the battery (the Charging LED is on), the Equalize LED will ash. Once the main 
charging cycle is complete, the Equalize cycle will begin and the Equalize LED will stay on all 
the time. If the Charging LED is off when the button is pressed, the Equalize cycle will begin 
immediately. 