Product Manual

6
* This is Analytic Systems’ suggested range. Please consult your battery manufacturer for their recommendations.
* Specications subjects to change without notice.
Installation
Allow at least 1 inch of clearance all around the case for cooling. The best mounting congu-
ration is to mount the unit on a vertical surface oriented as shown. Use #10 screws of the
appropriate type for the mounting surface to securely mount the unit.
There is 1500 volts (500V for 24V Input) of isolation between the input and output, and the
input and case. There is 500 volts (1500V for 48V Output) of isolation between the output and
case. Therefore, the unit may be mounted on any surface without fear of electrolysis or ground
fault.
General
Efciency > 80 % @ maximum output
Stages 2 or 3
Temp. Range -25 to +40
o
C @ maximum output
Isolation
Input-Output & Input-Case 1500 Vdc (500 Vdc @ 24 V In),
Output-Case 500 VDC (1500Vdc @ 48 V Out)
Length 9.6 in / 24.4 cm
Width 8.2 in / 20.8 cm
Height 3.5 in / 6.4 cm
Clearance 1 Inch (2.5 cm) all around
Material Marine Grade Aluminum
Finish Black Powder Epoxy
Fastenings 18-8 Stainless
Weight 7.0 lb / 3.2 kg
Designed and manufactured by: ANALYTIC SYSTEMS WARE (1993) LTD.
8128 River Way
Delta, BC V4G 1K5 Canada
p. 604.946.9981 f. 604.946.9983
tf. 800.668.3884 US/Canada
www.analyticsystems.com analyticinfo@analyticsystems.com Revised July 2014
INPUT
FUSE
TO
REMOTE
OUTPUT TERMINAL
ON/OFF
INPUT POWER
OUTPUT
FUSE