Product Specifications
8128 River Way, Delta B.C. V4G 1K5 Canada T. 604.946.9981 F. 604.946.9983 TF. 800.668.3884 (US/CANADA)
www.analyticsystems.com
An ISO9001 and AS9100 Registered Company Battery Chargers • Inverters • Power Supplies • Voltage Converters
Note: Specications are subject to change without notice.
DC
BATTERY CHARGER
MODEL
BCD305
Electrical (Input)
Model Number BCD305-12-12 BCD305-12-24
Input Volts (DC) 10.5 – 14 10.5-28
Input Amps (max) 30
Input Fuse (AGC) 20A x 2
Noise on Input < 10 mV
Low Input Voltage Alarm 10.5V
Electrical (Output)
Output Nominal (op) 12 24
Output Volts (DC) 13.6 ± 0.05 27.2 ± 0.05
Charging Current (Amps) *26 *13
Output Adjustment ± 0.5
Output Crowbar Programmed O/P Volts x (1.3 ±1%)
Output Fuse (AGC) 30A x 2
Output Ripple & Noise < 10 mV
Battery Banks 1 or 2
Stages 2
Battery Size (Amp Hours)* 104-156 52-78
Regulation (Line & Load) < +/- 0.5%
Duty Cycle Continuous 100% for 24 hours per day
Efciency > 85% @ Maximum Output
Environment Specication
Operating Temp. Range
-25° to +40°C @ maximum output
Derate Linearly 2.5% per °C from 40°C
(Optional -40°C extra wide temp. operation avail.)
Humidity
0 - 95% Relative Humidity
(non-condensing) with optional conformal coating
Audible Noise NONE Ødb @ 3 ft
Typical Service Life > 10 yrs. (87,600 hrs)
Isolation
Any Input or Output to Case 500 VDC
Input to Output – Common Negative
Mechanical Specication
Length 9.1 in / 23.1 cm
Width 7.8 in / 19.8 cm
Height 2.5 in / 6.4 cm
Material Marine Grade Aluminium
Finish Black Anodize
Fastenings All 18-8 Stainless Steel
Weight 4.0 lb / 1.8 kg
Connections Built to meet UL458 & CSA22.2.107.1
Warranty 3 years
Safety Designed to meet CSA 22.2.107.1 & UL458
*The Actual charging rate depends upon the input/output voltage ratio. To obtain the charging capability at any given input voltage, use the following formula: Charging Current = Input
Volts/Output Volts x 26. For example, at 11 VDC in and 13.6 VDC out, the charging current = 11/13.6 x 26 = 21.0 amps