DC BATTERY CHARGER
MODEL BCD 1015 SERIES
Electrical (Input)
Nominal (ip) 24 48 72
Actual (Vac) 20-35 40-60 65-90
Input Amps (max) 66.7 34 21
Input Fuse (ATC) 40 x 2 20 x 2 25 x 1
Noise on Input < 50mV
Electrical (Output)
Output Nominal (op) 12 24 48
Output Volts (DC) 13.6 ± 0.05 27.2 ± 0.05 54.4 ± 0.05
Absorption Voltage (Vdc) 14.4 28.8 57.6
Charging Amps 60 40 20
Absorption to Float 9 .0 Amps 6 .0 Amps 3.0 Amps
Output Adjustment (Vdc) ± 1.0V
Output Fuses (AGC) 40 x 2 40 x 2 25 x 2
Battery Banks 1 or 2 (3 Bank Option Available)
Battery Size (Amp Hrs.) 240-360 160-240 80-120
Output Crowbar 16.0 ± 0.5V 32.0 ± 1.0V 63.9 ± 2.0V
Output Ripple & Noise < 50 mV
Regulation (Line & Load) < +/- 0.5%
Temperature Comp. -30 mV/°C -60 mV/°C -120 mV/°C
Duty Cycle Continuous 100% for 24 hours per day
Efciency > 82.6% @ Maximum Output
Stages 2 or 3 (user selectable)
Environment Specication
Operating Temp. Range
-25° to +40°C @ maximum output Derate Linearly 2.5% per °C from 40°C
(Optional -40°C extra wide temp. operation avail.)
Humidity 0 - 95% Relative Humidity (non-condensing) with optional conformal coating
Audible Noise NONE Ødb @ 3 ft (34.5 dB when fan operating)
Typical Service Life > 10 yrs. (87,600 hrs)
Isolation Input-Case & Input-Output 1500VDC (500V @ 24V I/P)Output-Case 500VDC (1500VDC @ 48V O/P)
Mechanical Specication
Length 14.5 in / 36.8 cm
Width 9.9 in / 25.1 cm
Height 5.0 in / 12.7 cm
Clearance 1 inch (2.5 cm) all around
Material Marine Grade Aluminium
Finish Black Anodize / Powder Epoxy Coat
Fastenings All 18-8 Stainless Steel
Weight 12.0 lb / 5.5 kg
Connections Four contact output terminals
Warranty 3 years
Safety Designed to meet CSA 22.2.107.1 & UL458