Product Manual
6
* This is Analytic Systems’ suggested range. Please consult your battery manufacturer for their recommendations.
* Specications subjects to change without notice.
Installation
MOUNTING
Mount the unit in a DRY location. Allow at least 4 inches of clearance around the heat sink 
ns for adequate cooling. 
POWER CONNECTION
The unit is supplied with power leads about 3 feet long. This should normally be adequate to 
connect to a source of power. If you must extend the power leads, be sure to use at least a 
good quality (typeTEW) AWG8 wire. The wire colours are: 
All connections should be made inside an appropriate junction box. Refer to the specications 
table for the correct sizing of the circuit breaker in the distribution panel.
Red - Positive Black- Negative
Designed and manufactured by:  ANALYTIC SYSTEMS WARE (1993) LTD.
8128 River Way 
Delta, BC  V4G 1K5  Canada
p. 604.946.9981  f. 604.946.9983 
tf. 800.668.3884 US/Canada
www.analyticsystems.com analyticinfo@analyticsystems.com  Revised August 2014
General
Efciency > 80 % @ maximum output
Stages 2 or 3
Temp. Range -25 to +40o C @ maximum output
Isolation
Input-Output & Input-Case 1500 Vdc
Output-Case 500 VDC (1500Vdc @ 48 V Out)
Length 14.5 in / 36.8 cm
Width 9.9 in / 25.1 cm
Height 5.5 in / 14.0 cm
Clearance 1 Inch (2.5 cm) all around
Material Marine Grade Aluminum
Finish Black Anodize / Black Powder Epoxy
Fastenings 18-8 Stainless
Weight 12 lb / 5.5 kg