Product Manual

5
Introduction
The model BCA610 Battery Charger charges 12, 24, 32 or 48 batteries from a 110 or 220 VAC
power source. The all new Current Mode switching design offers increased power and reliabil-
ity in a compact package. Extra input and output ltering reduce EMI to extremely low levels.
Reliability features include an input fuse, thermal shutdown, current limiting, reverse battery
hookup protection and output short circuit shutdown with automatic recovery. The output
voltage is easily adjusted 1.0 volts above or below the standard output voltage to accommo-
date special charging requirements. High quality digital meters can be added (factory option)
to allow monitoring of charging current and charging voltage.
Features
In a DC UPS ( Un-interruptible Power Supply ) , the charger simultaneously powers the DC load
as well as the battery. As long as the AC power to the charger is available and the charger is
working normally, the charger will supply the DC load as well as charge / oat the battery. In
case the AC power fails or if the charger stops working, the battery will automatically power
the DC load. As soon as the AC power to the charger is restored, the DC load will once again
be fed by the charger and at the same time the battery will be recharged. CAUTION! Please
ensure that the sum of the current drawn by the DC load and the current desired for charging
the battery is less than the maximum current capacity of the charger. To use as a DC UPS, rst
switch off the DC load and connect it to the battery. Now connect the battery. Switch on the
charger and then switch on the DC load.
Specications
Input Voltages
Nominal (ip) 110 220
Actual (Vac) 90 – 130 180 - 260
Frequency (Hz) 45 - 65
Input Amps (max) 9.3 4.7
Input Fuse MDA-12 MDA-6