Product Specifications
8128 River Way, Delta B.C. V4G 1K5 Canada T. 604.946.9981 F. 604.946.9983 TF. 800.668.3884 (US/CANADA)
www.analyticsystems.com
An ISO9001 and AS9100 Registered Company Battery Chargers • Inverters • Power Supplies • Voltage Converters
Note: Specications are subject to change without notice.
AC
BATTERY CHARGER
MODEL
BCA1000
Electrical (Input)
Nominal (ip) 110 220
Actual (Vac) 90-130 180-260
Input Amps (max) 17 8.5
Input Fuse (MDA) 20A (12V) 25A all others 10A (12V) 15A all others
Input Frequency 45-65 Hz
Noise on Input < 50mV
Electrical (Output)
Output Nominal (op) 12 24 32 48 72
Output Volts (DC) 13.6 ± 0.05 27.2 ± 0.05 36.3 ± 0.05 54.4 ± 0.05 81.6 ± 0.05
Absorption Voltage (Vdc) 14.4 28.8 38.4 57.6 86.4
Charging Amps 60 40 30 20 13
Absorption to Float (15%) 9.0 Amps 6.0 Amps 4.5 Amps 3.0 Amps 2.0Amps
Output Adjustment (Vdc) ± 1.0V
Output Fuses (ATC) 40 x 2 40 x 2 40 x 2 25 x 2 15 x 2
Battery Banks 1 or 2 ( 3 Bank Option Available)
Battery Size (Amp Hrs.) 240 - 360 160 – 240 120 – 180 80 – 120 50-80
Output Crowbar 16.0 ± 0.5V 32.0 ± 1.0V 42.7 ± 1.3V 63.9 ± 2.0V 95.9± 4.0V
Output Ripple & Noise < 50 mV
Regulation (Line & Load) < +/- 0.5%
Temperature Comp. -30 mV/°C -60 mV/°C -80 mV/°C -120 mV/°C -180 mV/°C
Duty Cycle Continuous 100% for 24 hours per day
Efciency > 75% @ Maximum Output
Stages 2 or 3 (user selectable)
Environment Specication
Operating Temp. Range
-25° to +40°C @ maximum output
Derate Linearly 2.5% per °C from 40°C (Optional -40°C extra wide temp. operation avail.)
Humidity 0 - 95% Relative Humidity (non-condensing) with optional conformal coating
Audible Noise NONE Ødb @ 3 ft
Typical Service Life > 10 yrs. (87,600 hrs)
Isolation Input-Case & Input-Output 1500VDC Output-Case 500VDC (1500V @ 48V Output)
Mechanical Specication
Length 14.5 in / 36.8 cm
Width 9.9 in / 25.1 cm
Height 5.0 in / 12.7 cm
Clearance 1 inch (2.5 cm) all around
Material Marine Grade Aluminium
Finish Black Anodize / Powder Epoxy Coat
Weight 12.0 lb / 5.5 kg
Fastenings All 18-8 Stainless Steel
Connections Four contact output terminals
Warranty 3 years
Safety Built to meet UL458 & CSA22.2.107.1