Datasheet
ADP2114 Data Sheet
Rev. B | Page 26 of 40
OPERATION MODE CONFIGURATION
The dual-channel ADP2114 can be configured to one of the four
modes of operation by connecting the OPCFG pin as shown in
Table 7. This configuration sets the current limit for each
channel and enables or disables the transition to pulse skip mode
at light loads.
In the dual-phase configuration, the outputs of the two channels
are connected together, and they generate a single dc output
voltage, V
OUT
. For this single combined dual-phase output,
only Mode 2 in the OPCFG options can be used. In this mode,
the error amplifiers of both phases are used. The feedback
pins (FB1 and FB2) are tied together, the compensation pins
(COMP1 and COMP2) are tied together, the soft start pins (SS1
and SS2) are tied together, and the enable pins (EN1 and EN2)
are tied together.
In addition, if the power-good feature is used, combine PGOOD1
and PGOOD2 and connect them to VDD through a single
pull-up resistor.
When the ADP2114 is synchronized to an external clock, the
converters always operate in fixed frequency CCM, and they do
not enter into pulse skip mode at light loads. In this case, when
configuring the OPCFG pin, choose forced PWM mode.
Table 7. Current Limit Operation Mode and Configuration
Maximum Output Current Peak Current Limit
Mode R
OPCFG
(Ω) ± 5% I
OUT1
(A)/I
OUT2
(A) I
LIMIT1
(A)/I
LIMIT2
(A) Power Savings at Light Load
1
0 to GND
2/2
3.3/3.3
Pulse skip enabled
2 4.7 k to GND 2/2 3.3/3.3 Forced PWM
3 8.2 k to GND 3/1 4.5/1.9 Pulse skip enabled
4 15 k to GND 3/1 4.5/1.9 Forced PWM