Load Step of 50% to 75%
10180-046
Figure 47. Output Voltage Transient, 50% to 75% Load,
385 V DC, One Phase Only
Yellow Trace: Load Current, 5 A/div, 1 ms/div
Green Trace: Output Voltage (AC-Coupled), 200 mV/div, 1 ms/div
10180-047
Figure 48. Output Voltage Transient, 50% to 75% Load,
385 V DC, Both Phases Active
Yellow Trace: Load Current, 5 A/div, 200 µs/div
Green Trace: Output Voltage (AC-Coupled), 100 mV/div, 200 µs/div
10180-048
Figure 49. Output Voltage Transient, 75% to 50% Load,
385 V DC, One Phase Only
Yellow Trace: Load Current, 5 A/div, 1 ms/div
Green Trace: Output Voltage (AC-Coupled), 200 mV/div, 1 ms/div
10180-049
Figure 50. Output Voltage Transient, 75% to 50% Load,
385 V DC, Both Phases Active
Yellow Trace: Load Current, 5 A/div, 200 µs/div
Green Trace: Output Voltage (AC-Coupled), 100 mV/div, 200 µs/div