Datasheet
ADF4158 Data Sheet
Rev. E | Page 32 of 36
FAST-LOCK TIMER AND REGISTER SEQUENCES
If the fast-lock mode is used, a timer value needs to be loaded
into the PLL to determine the time spent in wide bandwidth mode.
When the DB[20:19] bits in Register 4 (R4) are set to 01 (fast-
lock divider), the timer value is loaded via the 12-bit clock divider
value. To use fast lock, the PLL must be written to in the
following sequence:
1. Initialization sequence (see the Initialization Sequence
section). This should only be performed once after
powering up the part.
2. Load Register R4 DB[20:19] = 01 and the chosen fast-lock
timer value (DB[18:7]).
3. Load Register R2 with the chosen CLK
1
divider value
(DB[14:3]) if longer time in wide loop bandwidth is
required.
Note that the duration that the PLL remains in wide bandwidth
is equal to the CLK
1
× fast-lock timer/f
PFD
, where CLK
1
is the
12-bit CLK
1
divider in Register R2.
In addition, note that the fast-lock feature does not work in
ramp mode.
FAST LOCK: AN EXAMPLE
If a PLL has a reference frequency of 13 MHz, that is, f
PFD
=
13 MHz, as well as CLK
1
= 10 (12-bit CLK
1
divider in Register R2)
and a required lock time of 50 µs, the PLL is set to wide bandwidth
for 40 µs.
If the time period set for the wide bandwidth is 40 µs, then
Fast-Lock Timer Value = Time in Wide Bandwidth × f
PFD
/MOD
Fast-Lock Timer Value = 40 µs × 13 MHz /10 = 52.
Therefore, 52 must be loaded into the clock divider value in
Register R4 in Step 2 of the sequence described in the Fast-Lock
Timer and Register Sequences section.
FAST LOCK: LOOP FILTER TOPOLOGY
To use fast-lock mode, an extra connection from the PLL to the
loop filter is needed. The damping resistor in the loop filter
must be reduced to ¼ of its value while in wide bandwidth
mode. This is required because the charge pump current is
increased by 16 while in wide bandwidth mode, and stability
must be ensured. To further enhance stability and mitigate
frequency overshoot while frequency change (in wide band-
width mode), Resistor R3 is connected. During fast lock, the
SW1 pin is shorted to ground and SW2 is connected to CP (it
is done by setting Bits DB[20:19] in Register R4 to 01—fast lock
divider). The following two topologies can be used:
• Divide the damping resistor (R1) into two values (R1 and
R1A) that have a ratio of 1:3 (see Figure 45).
• Connect an extra resistor (R1A) directly from SW1, as shown
in Figure 46. The extra resistor must be chosen such that
the parallel combination of an extra resistor and the damping
resistor (R1) is reduced to ¼ of the original value of R1.
For both of the topologies, the ratio R3:R2 should equal 1:4.
VCOCP
C1 C2 C3
R3
R2
R1
R1A
SW2
SW1
ADF4158
08728-032
Figure 45. Fast-Lock Loop Filter Topology—Topology 1
VCOCP
C1 C2 C3
R3
R2
R1R1A
SW2
SW1
ADF4158
08728-102
Figure 46. Fast-Lock Loop Filter Topology—Topology 2