ViewStat Communicating Thermostat - Programming Protocol Reference Guide
Programming Quick Reference (Cont.)
Command Description Value
Thermostat HVAC Operational Commands
SH Heat Mode Set Point Two digit integer: 40 - 88 for °F;
4 - 31 for °C
SH++ Increment heat set point Integer value which when added to the cur-
rent heat set point does not fall outside the
SH limits
SH-- Decrement heat set point Integer value which when deducted from
the current heat set point does not fall out-
side the SH limits
SC Cool Mode Set Point Two or three digit integer: 42 - 90 for °F;
6 - 33 for °C
SC++ Increment cool set point Integer value which when added to the cur-
rent cool set point does not fall outside the
SC limits
SC-- Decrement cool set point Integer value which when deducted from
the current cool set point does not fall out-
side the SC limits
S Current Mode Set Point Two or three digit integer (see next two
commands)
SP++ Increment current mode set point Integer value which when added to the cur-
rent mode set point does not fall outside
the SH and SC limits
SP-- Decrement active set point Integer value which when deducted from
the current mode set point does not fall out-
side the SH and SC limits
DIF1 Temperature control differential for 1st stage
heat/cool.
0.5° - 2° in 0.5° increments
DIF2 Temperature control differential for 2nd stage
heat/cool.
0.5° - 2° in 0.5° increments
OFFSET Amount to offset the display temperature from
the sensed temperature.
±3°, 1° increments
SHUM Humidify Mode set point Two digit integer: 10-90
SHUM++ Increment humidify set point Integer value which when added to the cur-
rent humidify set point does not fall outside
the SHUM limits
SHUM-- Decrement humidify set point Integer value which when deducted from
the current humidify set point does not fall
outside the SHUM limits
SDEH Dehumidify Mode set point Two digit integer: 10-90
SDEH++ Increment dehumidify set point Integer value which when added to the cur-
rent dehumidify set point does not fall out-
side the SDEH limits
SDEH-- Decrement dehumidify set point Integer value which when deducted from
the current dehumidify set point does not
fall outside the SDEH limits
MODE,M Thermostat Mode of Operation A / C / H / E / OFF
(Auto/Cool/Heat/EMHT/Off)
Humid/Dehum when operating as a humid-
ity controller.
FAN, F Fan Switch Setting A / ON (Auto/On)
HVAC, H Report HVAC Relay States Read Only