User Guide

ViewStat Installation and Wiring
28
ViewStat Communicating Thermostat
Start with address 1 and increment by 1 for each new address - do not skip an address.
This will optimize communications speed.
6. After the address has been selected, press the Enter button to store the address.
7. Use the Scroll Up and Scroll Down buttons to set the "Number of Stats on the Network" to the
highest address that will be on the thermostat network. This will be equal to the total number of
thermostats on the network (unless one or more addresses are skipped - see step 5).
8. Press Enter to set the baud rate. The ViewStat must be set for 9600 baud to communicate with
the miniverter. This is the default setting, and you shouldn’t ever change this setting.
9. Press Enter to "Exit" the Communications Set Up sub-menu. This will return you to the main
menu.
10. Press the Scroll Down button until "Exit" is displayed. Press the Enter button. The thermostat
will then reset and return to normal operation.
Write down the address for each thermostat.
This number must be set the same at each thermostat.