User Guide
ViewStat Installation and Wiring
21
V
iewStat Communicating Thermostat
Wiring the Thermostat
1. Strip 1/4" (0.63 cm) of insulation from each wire to be used.
2. Secure wires into the terminals on the base according to the appropriate wiring diagram, as
described in the following table. Refer to the Wiring Diagrams section on page 29. Use color-
coding practices (i.e. white wire to W terminal) whenever possible.
3. Check each wire to ensure it is securely fastened, not broken, and exposed wires are not
touching.
Communication and Equipment terminal wiring definitions
The following table describes the Communication and Equipment terminal wiring definitions (see
FIG. 5 on page 10).
• Single Stage Furnace & AC Refer to FIG. 18 on page 29
• Two Stage Furnace & Two Stage AC Refer to FIG. 19 on page 30
• Roof Top Unit (Two Stage Heat & Two Stage Cool) Refer to FIG. 20 on page 31
• Boiler with AC (Two Transformers) Refer to FIG. 21 on page 32
• Single Stage Heat Pump Refer to FIG. 22 on page 33
• Two Stage Heat Pump Refer to FIG. 23 on page 34
• First Stage Radiant Floor Heat
Second Stage Furnace One Stage of Cooling
Refer to FIG. 24 on page 35
Communication and Equipment Terminal Wiring Definitions
Communication Terminal
C Thermostat Voltage (common)
R Thermostat Voltage (hot)
RSR (support module) Thermostat Voltage (hot)
RSC (support module) Thermostat Voltage (common)
RSB/RSA (support module) Support module communication (half-duplex)
REF Ground Reference
B-/B+ Receive
A-/A+ Transmit
Equipment Terminal
RC Switched Voltage (cool)
RH Switched Voltage (heat)
RV COOL (O) Reversing Valve - Cool (energized in Cool mode)
RV HEAT (B) Reversing Valve - Heat (energized in other modes)
GFan
HUM/W1 1st stage Heat (non-heat pump)
-or-
3rd stage Heat AND 1st Stage Emergency Heat (heat pump)
-or-
Humidification (with humidity control sensor)