Operating instructions

NI cRIO-9030 Operating Instructions and Specifications | © National Instruments | 27
Figure 18. Installing a Ferrite on Two USB Cables
Refer to Figure 1 for the location of the two USB host ports on the cRIO controller. Refer to
Table 2 for USB host port pin locations and signal descriptions.
Caution Do not hot-swap USB devices while the cRIO controller is in a hazardous
location or connected to high voltages. If the cRIO controller is not in a hazardous
location, you can connect and disconnect USB devices without affecting operation.
USB Device Port
The USB device port, shown in Figure 1, is intended for use in device configuration, application
deployment, debug, and maintenance. For example, you can install software or driver updates
through the USB device port during field maintenance instead of interrupting communication on
the RJ-45 Ethernet ports.
Caution National Instruments requires a locking USB cable, such as part number
157788-01, in order to meet the shock and vibration specifications of this product.
Table 2. USB Host Port Pin Locations
Pinout Pin Signal Name Signal Description
1 VCC Cable power (+5 V)
2 D- USB data-
3 D+ USB data+
4 GND Ground
1
4
2
3