Operating instructions
NI cRIO-9030 Operating Instructions and Specifications  | © National Instruments | 19
Figure 6. cRIO-9030 Front View with Dimensions
Caution  Your installation must meet the following requirements for space and 
cabling clearance:
• Allow 25.4 mm (1.00 in.) on the top and the bottom of the controller for air 
circulation, as shown in Figure 7.
• Allow 50.8 mm (2.00 in.) in front of modules for cabling clearance for 
common connectors, such as the 10-terminal, detachable screw terminal 
connector, as shown in Figure 8.
Figure 7. cRIO-9030 Front View with Cooling Clearance
NI cRIO-9030
88.11 mm
(3.47 in.)
8.55 mm
(0.34 in.)
117.20 mm
(4.61 in.)
107.00 mm
(4.21 in.)
219.48 mm
(8.64 in.)
NI cRIO-9030
25.40 mm (1.00 in.)
COOLING DIMENSIONS
25.40 mm (1.00 in.)
COOLING DIMENSIONS