Specifications
Compatible Ballast Information
20
RADIA Lighting Control System
DC-Controlled Electronic Ballasts (4-Wire Ballasts)
The DC-controlled Electronic Ballasts track a 0-10 or 0-12 VDC channel for dimming and an AC switch
channel for on/off. This ballast design is better than magnetic, but many stop dimming at about 20%
brightness. That's fine for energy management and secondary lighting zones, but not for primary lighting that
requires precision, low-level dimming control.
The following table lists compatible DC-controlled electronic ballasts.
Ballast Interfaces and 2-Wire Ballasts
In some cases, dimmers are wired to ballast interfaces (provided optionally by lighting suppliers), rather than
directly to the ballasts. A few interfaces are driven from a standard AMX Lighting incandescent channel, while
most use FDB dimming configurations.
The following table lists compatible ballast interfaces.
DC-controlled electronic ballasts (4-wire ballasts)
Manufacturer Style Model Volts AMX Lighting modules
Advance Mark VII All models 120 RDM-HDC
Advance Mark VII All models 277 RDM-HDC
RDM-DC
RDM-2DC
RDM-3DC
Lightolier PowerSpec HDF See Ballast interfaces
Magnatek TRIAD B232SR120V20 120 RDM-HDC
Magnatek TRIAD B232SR277V20 277 RDM-HDC
Motorola Helios M2-RN-T8-10C-120 120 RDM-HDC
Motorola Helios M2-RN-T8-10C-277 277 RDM-HDC
Prescolite Intelect PUV series 120 RDM-HDC
Prescolite Intelect PUV series 277 RDM-HDC
Ballast Interfaces and 2-Wire Ballasts
Manufacturer Style Model Volts AMX Lighting modules Note
Advance Mark X All models 277 RDM-INC
Lightolier • DA10 HDF
• DA20HDF
PowerSpec HDF 277 RDD-DM4, RDD-DM6, RDM-MDM,
RDM-INC, RDM-2INC, and RDM-INC50
1
Lutron HP-2/4/6 Interfaces HiLume FDB 120 RDD-DM4, RDD-DM6, RDM-MDM,
RDM-INC, RDM-2INC, and RDM-INC50
2
Lutron GRX-FDBI HiLume FDB 120 RDD-DM4, RDD-DM6, RDM-MDM,
RDM-INC, RDM-2INC, and RDM-INC50
3
Prescolite CIB Interface Intelect ballasts 120 RDD-DM4, RDD-DM6, RDM-MDM,
RDM-INC, RDM-2INC, and RDM-INC50
4
Prescolite CIB Interface Intelect ballasts 277 RDD-DM4, RDD-DM6, RDM-MDM,
RDM-INC, RDM-2INC, and RDM-INC50
4
Notes:
1. The Lightolier ballasts require a proprietary DC-signal interface (including low-level trim). The AMX
Lighting controller module handles load power.
2. The Lutron HP-2, 4, and 6 interfaces accept 120 VAC input. The load can be 120/277 VAC (including low-
level trim). Interface includes power control to ballasts.
3. The Lutron GRX-FDBI accepts 120 VAC input. The load must be 120 VAC. Interface includes power
control to ballasts.
4. The Prescolite ballast interfaces are optional. The AMX Lighting controller handles load power.