Specifications
Installation
9
RADIA Lighting Control System
RDA-ENC6B 120/240 VAC Line Input (Single Phase)
FIG. 10 shows a 120/240 VAC single-phase (3 W + G) wiring diagram for the RDA-ENC6B line input
terminal block.
Connecting High-Voltage, Three-Phase Input Power and Loads
Follow these steps to wire high-voltage (120 VAC and 240 VAC), three-phase power connections (FIG. 11) to
any of the AMX Lighting modules.
1. Connect the green ground wire(s) to the copper ground lug on the enclosure. Ensure the ground wire is
properly connected to earth ground.
2. Connect the white neutral wire(s) to one of the terminals on the enclosure's neutral terminal block.
3. Provide a separate neutral wire for each controlled zone.
4. Connect the black line input from the electrical panel to the enclosure's line terminal. The line input
terminal accepts a 0 AWG copper conductor.
5. Connect load lines from the electrical devices to the Load terminals. Load 1 applies to dimmer 1, Load 2
applies to dimmer 2, and so on.
FIG. 10 RDA-ENC6B 120/240 VAC single-phase (3 W + G) wiring diagram
FIG. 11 High-voltage, three-phase input power
12a2b3
12a2b3
RDA-ENC6B
Connect to neutral block
line input terminal
These
connections
are factory-
wired