User Guide

Installation Sheet
RDD-DM4 4-Channel Integrated Dimmer Module 120,240,277 VAC
The RDD-DM4 Four-Channel Integrated Dimmer Module controls up to six
dimmed channels with four 1200 W onboard dimmers and two satellite
connectors (for RDM series dimmer or switching modules). It is designed
for use with the RDA series of enclosures, in an AMX Lighting™ modular
digital dimming system. The RDD-DM4 is controlled by AXlink, PROlink, or
by dry (contact) closures. The RDD-DM4’s 120, 240, or 277 VAC ratings are
CE, UL, and C-UL approved.
RDD-DM4 UL and C-UL Ratings: (per circuit)
Input
120, 240, 277 VAC, single phase, 3-wire, 50/60 Hz, 2400 W, one feed
120 ,240, 277 VAC, single phase, 4-wire, 50/60 Hz, 4800 W, dual feed
Output
1200 W max. per channel @120, 240, 277 VAC
2400 W max. total, all four channels on with 2400 W feed
4800 W max. total, all four channels on with dual 2400 W feeds
Feed circuit #1 goes to dimmer 1 and 3; feed circuit #2 goes to dimmer
2 and 4.
Specifications
Dimensions (HW): 5.87" x 10.0" (149.00 mm x 254.00 mm)
Use wires rated at 75°C (167°F)
Torque terminals to 20 in-lbs (2.3 N/M)
Max. wire size: 10 AWG (4 mm²)
Wire stripping length: 0.35" (9 mm)
Weight: 4.5 lbs (2.04 kg)
BTU/hr: 300 single feed (2400 W); 600 dual feed (4800 W)
Power consumption: 50 mA @ 120 VAC, 25 mA @ 240 VAC, 22 mA
@ 277 VAC
Control port current: 200 mA @ 12 VDC
Loads:
Button/Jumper Information:
RESET button: By pressing the RESET button, located on the
RDD-DM4 circuit board, it is possible to restart the processor without
having to power-down the unit or disconnect AXlink or PROlink.
RESET does not affect any saved presets or curve settings.
MEMORY PROTECT on/off jumper: The MEMORY PROTECT
jumper is set to Off by default. When put in the On position, saved
curve settings and presets are protected in case of a power failure.
Caution: Pre-Installation Notes
All Class 1 wiring must be connected to proper terminals.
All control wiring must be connected to proper terminals.
Disconnect power while installing or connecting the unit.
Keep top and bottom air vents clear at all times.
Test loads for shorts before connecting.
Use low-voltage wires with a 300 volt rating or greater.
Use field-installed copper conductors.
All electrical ratings are for continuous duty.
For indoor use only.
AC lighting loads only.
This module may require extra power from the AXlink connection or an
external power supply connected to the control card.
Connecting the RDD-DM4 to the AMX Lighting Master
Connecting AXlink:
Connect the 4-pin captive-wire AXlink from the RDD-DM4 to the Central
Controller for AXlink control of the dimming system.
Connecting PROlink:
Connect the orange 4-pin captive-wire PROlink connector from the
RDD-DM4 to a PRO-DP8 PROlink wall panel.
FIG. 1 RDD-DM4 4-channel Integrated Dimmer Module
Mounting
points
Power
device
Bridge
Line In
High-voltage
connections
Load out
AXlink
address
DIP switch
PROlink
address
DIP
switch
Low-voltage
control
wiring: 4-pin
connectors
to RDM
series modules
PROlink
External
+12 V
power
connector
(optional)
Memory
Protect
jumper
Reset
button
Chokes
Neutral
AXlink
connector
Dry Closures
Suggested Loads
Dimmed Switched (at 600 W)
Incandescent Fans
Low-voltage Florescent ballast
Neon, cold-cathode Motors
FIG. 2 RDD-DM4 connections
FIG. 3 Connecting AXlink
FIG. 4 Connecting PROlink
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
3 (-)
1 (+)
RDD-DM4 4-pin module connector
4-pin plug from RDM series module
NOTE: The 4-pin plugs from the module connector to
the 4-pin connector on the master (black plug cover facing up).
PWR
AXP
AXM
GND
PWR
AXP
AXM
GND
Central
RDD-DM4
Controller
(optional)
PRO-DP8 Pack 1 Pack 2
+12
PR+
PR-
GND
+12
PR+
PR-
GND

Summary of content (2 pages)