User`s manual

6
Area and Site Applications
For outdoor parking area applications, lighting should be dimmed or turned off within one hour of business closing. Scheduled dimming and occupancy detection can be
combined to reduce maximum lighting levels outside business hours yet ensuring egress and security lighting is available on occupancy detection.
40' Maximum
Mounting Height
Parking Surface
Sides of Drive Fixture Location
Fixture Spacing = 160' x 120' on Center.
20 xtures per 60' wide drive lane; 40 xtures total for 420' x 120' parking deck.
160' 160'
150'
Max.
60'
60'
Gateway
Building
Electrical Closet
Router
LumaWatt Energy
Management Server
CAT5 cable
up to 330'
LumaWatt sensor, one per fixture (Typical)
IESNA IESNA Lighting Handbook 10th Edition
Illuminance Values for Area and Site Applications
Parking Lot Design Guide
Illuminance
Minimum
Horizontal
Illuminance
1
Uniformity
Ratio
Max. / Min.
Minimum
Vertical
Illuminance
2
lux/fc
Basic 2.0 / 0.2 20:1 1.0 / 0.1
Basic
Enhanced
Security
5.0 / 0.5 15:1 2.5 / 0.25
Security 10.0 / 1.0 15:1
5.8-8.0 /
0.5-0.5
High
Security
30.0-60.0 /
3.0-6.0
4:1
12-60 /
1.2-6.0
NOTES: 1 Measured on parking surface without
shadowing from any object. 2 For facial recognition measured
at 5' above the parking surface at the point of lowest
horizontal illuminance.
Energy Savings Calculations
Conguration
Daily Hours
of Operation
Control Event
Annual Load
(KWh)
14 Sensor Integrated Luminaires 35' Mounting Height, Centered 120' x 160'
Bill-of-Material (BOM)
(1) RF-EM1, (1) RF-ROUT1, (1) RF-GW1
(14) GLEON-AA10-LED-E1-T2-BZ-DIMRF-LN (515W)
11 100% On 28,948
Control Schedule
7:30pm-11:30pm 4 100% On 10,526
11:30pm-6:30am
7
40% On, On
Occupancy
70%
7,268
Total Controlled Load 11 2 Events 17,895
Energy Saving 38%