User`s manual
5
Parking Garage Applications
Parking garage overall energy conservation and peak load reduction can be maximized by combining time scheduling, dimming on vacancy and daylight harvesting
strategies. Following the example below, an energy saving of 38% is possible in an enclosed parking garage. Perimeter luminaires may be grouped together and programmed
to dim, should natural lighting be available.
IESNA Lighting Handbook 10th Edition
Illuminance Values for Parking Garage Applications
Horizontal
Illuminance
Minimum Horizontal
Footcandles (FC)
Basic 1.0
Horizontal footcandle readings taken at oor level.
Uniformity Requirements for Horizontal Reading
Average to minimum (A/M) footcandle levels not to exceed
ratio of 4:1.
Maximum to minimum (M/M) footcandle levels not to exceed
ratio of 10:1.
Vertical
Illuminance
Minimum Horizontal
Footcandles (FC)
5' Above nished oor (AFF) at
lowest horizontal footcandle area.
0.5
Vertical footcandle readings taken at walls to the side of drive
lanes at 5' above nished oor (AFF).
Deck Ceiling
Deck Floor
Ceiling
Height
10'
Mounting Height/
Bottom of T-Joist
8'6"
Sides of Drive Fixture Location
Fixture Spacing = 30' on center with 30' between xtures above parking bays.
20 xtures per 60' wide drive lane; 40 xtures total for 300' x 120' parking deck.
15'
15'
30'Gateway
CAT5 cable up to 330'
LumaWatt sensor, one per fixture (Typical)
30'
30'
30'
Building
Electrical Closet
Router
LumaWatt Energy
Management Server
Energy Savings Calculations
Conguration
Daily Hours
of Operation
Control Event
Annual Load
(KWh)
40 Sensor Integrated Luminaires 8' Mounting Height (Enclosed Space)
Bill-of-Material (BOM)
(1) RF-EM1, (1) RF-ROUT1, (1) RF-GW1
(40) VPL-B03-LED-E1-WQ-AP-TMB-DIMRF-LW (73W)
24 100% On 25,579
Control Schedule
6:30am-9:30am 3 100% On 3,197
9:30am-4:00pm 6.5
50% On, On
Occupancy
100%
3,463
4:00pm-7:00pm 3 100% On 3,197
7:00pm-6:30am 11.5
50% On, On
Occupancy
100%
6,128
Total Controlled Load 24 4 Events 15,987
Energy Saving 38%