User Guide
Wiring and Installation
12
PRO-DP16 Decor 16-Button PROlink Wall Panel
Troubleshooting
The following table gives solutions to the most common installation problems.
Solutions to Common Installation Problems
Problem Resolution
Presets fade erratically. Check phasing.
Panel LED stays on. Check the PROlink wiring, Pack number, and dimmer
Pack settings.
Cannot select zones 1 - 6. Check Pack number and mode settings.
No operation. Check PROlink wiring/power connections.
All lights stay On. Check dimmer DIP switch settings and disconnect/
reconnect PROlink.
In Preset Recall Mode, Presets can be recalled, but
the Up and Down buttons (pushbuttons 14 and 15) do
not work.
Check Pack numbers. Verify that Packs are set for
1 - 10.