Specifications

Appendix B - Troubleshooting
79
NXV-300 Modero Virtual Touch Panel
Appendix B - Troubleshooting
This section describes the solutions to possible hardware/firmware issues that could arise during the
common operation of a Modero touch panel.
Troubleshooting Information
Symptom Solution
When using G4 WebControl to
communicate with a target panel, a
VNC Server dialog appears on my
screen.
During a WebControl connection to a target panel, a G4
Authentication dialog will ask you to enter the assigned password for
the panel before allowing access.
If prompted with a VNC Server dialog, enter the IP Address of the
target panel. This can be found within the Setup > Protected Setup
> System Connection page. This IP Address of the panel appears
within the IP Settings section of this page
Enter the IP Address and click OK. When prompted with the G4
Authentication popup, enter the panel’s WebControl password.
My Modero panel isn’t appearing
in my Workspace window.
Verify that the System number is the same on both the NetLinx
Workspace window and the System Connection page on the Modero
panel.
Verify that you have entered the proper NetLinx Master IP and
connection methods into the Master Connection section of the
System Connection page.
My Modero panel can’t obtain a
DHCP Address
In requesting a DHCP Address, the DHCP Server can take up to a few
minutes to provide the address.
Verify that an active Ethernet connection is attached to the rear of the
Modero before beginning these procedures.
•Select Diagnostics > Network Address from the Main menu and
verify the System number.
If the IP Address field is still empty, give the Modero a few minutes to
negotiate a DHCP Address and try again.
NetLinx Studio only detects one of
my connected Masters.
Each Master is give a Device Address of 00000.
Only one Master can be assigned to a particular System number.
When working with multiple Masters, open different instances of
NetLinx Studio and assign each Master its own System value.
Example: a site has an NXC-ME260/64 and an NI-4000. In order to
work with both units. The ME260/64 can be assigned System #1 and
the NI-4000 can then be assigned System #2 using two open
sessions of NetLinx Studio 2.
I can’t seem to connect to a
NetLinx Master using NetLinx
Studio 2.
From the Settings > Master Comm Settings > Communication
Settings > Settings (for TCP/IP), uncheck the "Automatically Ping
the Master Controller to ensure availability" box.
The pinging is to determine if the Master is available, and to reply
with a connection failure instantly if it is not. Without using the ping
feature, you will still attempt to make a connection, but a failure will
take longer to be recognized. Some firewalls and networks do not
allow pinging, though, and the ping will then always result in a failure.
When connecting to a NetLinx Master controller via TCP/IP, the
program will first try to ping the controller before attempting a
connection. Pinging a device is relatively fast and will determine if the
device is off-line, or if the TCP/IP address that was entered was
incorrect. If you decide NOT to ping for availability and the controller
is off-line, or you have an incorrect TCP/IP address, the program will
try for 30-45 seconds to establish a connection.
Note: When trying to connect to a master controller that is behind a
firewall, unchecking this option may be required. Most firewalls will not
allow ping requests to pass through for security reasons.