User Guide
NXA-UPS1500 Uninterruptible Power Supply
3
NXA-UPS1500 Uninterruptible Power Supply
Front Panel LCD
FIG. 2 describes the elements of the front panel LCD:
NXA-UPS1500 Product Specifications (Cont.)
Protection:
Overload: • AC Mode: >110% Buzzer continuously alarms, and shuts down in 10
minutes.
• Inverter Mode: >120% Buzzer continuously alarms, and shuts down in 10
seconds.
Self-Diagnostics: Upon Power-on
Short Circuit: • AC Mode: Breaker and electronic circuit
• Inverter Mode: Shut down automatically in 8 cycles
Alarms:
Audible and Visual: • Line Failure
• Battery Low
• Overload and Fault
Environment:
Operation Temperature: 32° - 104°F (0-40° C)
Operation Humidity: 95% RH Maximum, non-condensing
Dimensions (HWD): • 3.46” x 17.32” x 18.97” (8.80cm x 44.0cm x 48.2 cm)
• 2U rack height
Control Communication: RS-232
Certifications: • EN50091-1-1:1996 (Safety)
• FCC Part 15, Subpart B - Class A
Included Accessories • AC Input Power Cord
• Four 12V batteries (57-0678-SA) - included with the US/120V version only
• Tower and rack-mounting accessories
Other AMX Equipment: • NXA-UPS1500 EPM Extended Power Module (FG 678-16)
FIG. 2
Elements Of The Front Panel LCD
1. Utility (Green LED)
2. Fault (Red LED)
3. On Switch
4. Off Switch
5. Battery Replacement
6. Battery Backup (Amber LED)
7. Battery Low
8. Bypass
9. Utility Low, UPS Boost
10. Utility High, UPS Buck
11. UPS Output Indicator
12. Polarity Error or Ground Fault
13. Overload
14. Load/Battery Level (%)
15. Load/Battery Level
1234
5
6
7
891011
12 13
14
15
1
6
2
Indication Control Button