User Guide

NXA-UPS1500 Uninterruptible Power Supply
2
NXA-UPS1500 Uninterruptible Power Supply
Product Specifications
NXA-UPS1500 Product Specifications
Available Models: US version (110 Vac) - FG 678-15
Int’l version (220 Vac) - FG 678-20
Input:
Voltage Window:
(DIP Switch selectable)
US version - 110/115/120 Vac +35% ˜ -32%
Int’l version - 220/230/240 Vac +35% ˜ -32%
Frequency 45 ˜ 65Hz (50/60Hz auto-sensing)
Output:
Voltage Window (AC Mode): US version - 110/115/120 Vac +8% ˜ -12%
Int’l version - 220/230/240 Vac +8% ˜ -12%
Voltage Window (INV Mode): US version - 110/115/120 Vac +/-5%
Int’l version - 220/230/240 Vac +/-5%
Capacity (VA/W): 1500/900
Wave Form: Pure sine wave
Frequency: 50Hz/60Hz +/-0.1Hz
Transfer Time: 2 ms typical
Autonomy: > 8 min.
DC Start: Yes
Battery:
Type: 12V, sealed lead acid maintenance-free
Capacity: 9AH
Quantity: 4 12V batteries required (included with the US/120V version)
Voltage: 24 Vdc
Recharge Time: 2 ˜ 4 hours to 90%
Storage: Store at -15 to +30 °C (+5 to +86 °F), charge the UPS battery every 6
months.
Store at +30 to +45 °C (+86 to +113 °F), charge the UPS battery every 3
months.
Display:
LED: Utility mode
Backup mode
Battery conditions
LCD: Load level (%)
Battery level (%)
•Bypass
AVR-Boost/AVR Buck
Battery Low/Replace/Fault
UPS Fault
Site Wiring Fault
Overload