Specifications
Installation
10
NXA-PDU-1508-8 Power Distribution Unit
Power Outlets 1-8
The eight 110-220VAC 50/60Hz, IEC C-13, 15A AC Power Outlet Connectors provide AC power to
connected devices (see FIG. 7).
Power Inlet
The IEC C-14, 15A power inlet connector provides 110-220VAC, 50/60Hz mains power to the PDU.
Powering Up The NXA-PDU-1508-8
When power is applied to the PDU for the first time, the outlets are powered in sequence (1-8), with a delay of
0.5 second between outlets.
By default, the state of all outlets upon initial power-up is ON.
Initial Response Time
Allow the PDU approximately ten seconds after it appears online to register internal processes before
attempting to turn on a channel.
Persistence of On/Off States for All Outlets
By default, Persistence for all outlets is set to ON.
Persistence can be turned off via the PERSIST Send_Command (page 11).
For subsequent power-ups (from a power off state or on system reset), the PDU will restore the last recorded
state of any outlet in a sequenced fashion, starting from outlet 1 in numerical order, with a delay of 0.5 second
between energizing any two outlets, assuming the default Persistence setting of ON has not been changed.
Maximum load on a single outlet = 10A @ 110-120 VAC / 8A @ 220-240VAC.