Owner`s manual

Expansion Tanks
Honeywell Water Product Solutions
63-8702 53
TK300 Series Expansion Tanks- Heating
Honeywell Expansion Tanks are designed to absorb hot water
expansion in closed heating systems. They are equipped with
butyl diaphragms to separate the air from the system water
(glycol). The tanks are a welded, not clamped design. Pre-
pressurized at 12 psi, the tank keeps fluids circulating and
maintains minimum system pressure. Honeywell tanks resist
waterlogging, loss of pressure through relief valve spills, loss of
BTUs and reduce circulator running time. Use the super efficient
Honeywell PowerVent or air vents to remove air and micro-bubbles
from the system for maximum performance.
Butyl/EPDM diaphragm- 9 times better than natural rubber
Deep-drawn steel tank
Controls system pressure
Air-tight cushion-factory pre-charged to 12 psig and 100% tested
Maximum Operating Temperature: 240 F (115 C)
Maximum Operating Pressure: 100 psi (689 kPA)
Materials: steel shell, heavy duty butyl diaphragm
Comments:
Heating
Product Number
Connection
Size (inch)
Connection
Type
Diameter Height Volume
Maximum
Acceptance
Volume Weight
(inch) (mm) (inch) (mm) (gal) (L) (gal) (L) (lb) (kg)
TK300-15 1/2 in. NPT Male 8 in. 203.2 mm 12 5/8 in. high 321 mm high 2.0 gal
7.6 L
1 gal
3.8 L
5 lb 2.3 kg
TK300-30 1/2 in. NPT Male 11 in. 279.4 mm 15 1/2 in. high 394 mm high 4.4 gal
16.7 L
2.5 gal
9.5 L
9 lb 4.1 kg
TK300-60 1/2 in. NPT Male 11 in. 279.4 mm 23 in. high 584 mm high 7.6 gal
28.8 L
2.5 gal
9.5 L
14 lb 6.4 kg
TK300-90 1/2 in. NPT Male 15 3/8 in. 390.5 mm 21 in. high 533 mm high 14.0 gal
53.1 L
11.5 gal
40.1 L