User's Manual

Table Of Contents
Protected Setup Pages
63
MVP-9000i Modero® Wireless Touch Panel with Intercom
Selecting between these three immediately and automatically resets the existing password to the default
password for that setting. With an unsecured panel using the Standard setting, the default password is 1988.
With panels using either the Secure or the DoD settings, the default password is Amx1234! (paying attention
to the case of the letters). Entering the existing password will not work, and the default will need to be entered
at this point to allow access to the Protected Setup page and allow resetting of the password to a new one.
For more information on configuring AMX devices for a secure environment, please refer to the guide Security
Profiles: Configuring AMX Devices For Installation Into a Secure Environment, available at www.amx.com.
Security Profile Features
Standard: Factory default, shipped in this configuration.
Administrator and NetLinx user accounts have a default password of “password”.
Telnet, HTTP, HTTPS, and SSH are all enabled and require no authentication.
Program terminal requires no authentication.
ICSP communication protocol between devices: encryption and authentication are
disabled.
FTP is enabled.
Minimum password requirement is 4 characters.
Secure: Must be configured from the program terminal.
HTTP, Telnet, and FTP are disabled.
SSH, HTTPS, and program terminal require authentication by an authorized user.
SSH, HTTPS, and program terminal session timeouts are enabled.
ICSP communication protocol between devices: encryption and authentication are
enabled.
Minimum password requirement is 8 characters with at least 1 numeric character.
Login failure attempt pauses 4 seconds before another login attempt is allowed.
After 3 consecutive unsuccessful login attempts, login lockout is enabled for 15
minutes.
Login and logout audit logging is enabled.
DoD: Must be configured from the program terminal.
HTTP, Telnet, and FTP are disabled.
SSH, HTTPS, and program terminal require authentication by an authorized user.
SSH, HTTPS, and program terminal session timeouts are enabled.
ICSP communication protocol between devices: encryption and authentication are
enabled.
Minimum password requirement is 8 characters with at least 1 numeric character, one
uppercase character, one lowercase character, and one special character, with no
duplicate adjacent characters.
Login failure attempt pauses 4 seconds before another login attempt is allowed.
After 3 consecutive unsuccessful login attempts, login lockout is enabled for 15
minutes.
Login and logout audit logging is enabled.
DoD session banner is enabled.
If the Security button setting is changed in any way, even if it is toggled back to its
original setting, the password is automatically reset to the default for the chosen
setting. You MUST use the new default of 1988 (Standard) or Amx1234! (Secure or
DoD) to re-enter the Protected Setup page.