Specifications

Configuring Communication
34
MVP-5200i Modero® ViewPoint® Touch Panel with Intercom, 5.2 and 5”
10. Press the Reboot button to reboot the device and confirm changes.
Master Connection to a Virtual Master
Before beginning:
1. If making a Master connection via Ethernet, verify that the panel has been configured to communicate
with the Access Point.
2. In NetLinx Studio, select Settings > Master Communication Settings from the Main menu to open the
Master Communication Settings dialog (FIG. 35).
3. Click the Communications Settings button to open the Communications Settings dialog (FIG. 36).
4. Click on the Virtual NetLinx Master radio button (from the Platform Selection section) to indicate that
you are working as a NetLinx Master.
5. Click on the Virtual NetLinx Master radio box from the Transport Connection Option section to
indicate wanting to configure the PC to communicate with a panel. Everything else, such as the
Authentication, is greyed out because the procedure is not being made through the Master’s UI.
If configuring the panel to communicate with a Virtual Master on your PC via wireless
Ethernet, the Master IP/URL field must be configured to match the IP Address of the
PC. Make sure to use the Virtual System value assigned to the Virtual Master within
NetLinx Studio.
FIG. 35 Master Communications Settings dialog
FIG. 36 Communications Settings dialog