Specifications
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-13
Parameter Explanation Settings
Factory
Setting
Custome
r
06-12
Under-Current
Detection Level
00~100% (00: Disabled)
00
06-13
Under-Current
Detection Time
0.1~ 3600.0 sec
10.0
00: Warn and keep operating
01: Warn and ramp to stop
02: Warn and coast to stop
06-14
Under-Current
Detection Mode
03: Warn, after coast to stop, restart (delay
06-15 setting time)
00
06-15
Under-Current
Detection Restart
Delay Time (Lv)
1~600 Min.
10
00: Disabled
230V: 220 to 300VDC
460V: 440 to 600VDC
00
06-16
User-Defined Low-
Voltage Detection
Level
575V: 520 to 780VDC
06-17
User-Defined Low-
Voltage Detection
Time
0.1~ 3600.0 sec 0.5
06-18 Reserved
Group 7 Motor Parameters
Parameter Explanation Settings
Factory
Setting
Custome
r
07-00 Motor Rated Current 30 to 120% 100
07-01
Motor No-Load
Current
01 to 90% 40
07-02
Torque
Compensation
0.0 to 10.0 0.0
07-03 Slip Compensation
(Used without PG)
0.00 to 3.00 0.00
07-04 Number of Motor
Poles
02 to 10 04
07-05
Motor Parameters
Auto Tuning
00: Disable
01: Auto tuning R1
02: Auto tuning R1 + no-load test
00
07-06
Motor Line-to-line
Resistance R1
00~65535 mΩ
00
07-07 Reserved
07-08 Motor Rated Slip 0.00 to 20.00 Hz 3.00
07-09
Slip Compensation
Limit
0 to 250% 200
07-10 Reserved
07-11 Reserved