Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-11
Parameter Explanation Settings
Factory
Setting
Customer
05-22 Time Duration of 6th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-23 Time Duration of 7th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-24 Time Duration of 8th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-25 Time Duration of 9th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-26 Time Duration of
10th Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-27 Time Duration of
11th Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-28 Time Duration of
12th Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-29 Time Duration of
13th Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-30 Time Duration of
14th Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
05-31 Time Duration of
15th Step Speed
00 to 65500 sec or 00 to 6550.0 sec 00
00: 1 sec
05-32 Time Unit Settings
01: 0.1 sec
00
05-33
The Amplitude of
Wobble Vibration
0.00~400.00 Hz
0.00
05-34
Wobble Skip
Frequency
0.00~400.00 Hz 0.00
Group 6 Protection Parameters
Parameter Explanation Settings
Factory
Setting
Custome
r
230V series: 330.0V to 410.0V 390.0V
460V series: 660.0V to 820.0V 780.0V
575V series: 825.0V to1025.0V 975.0V
06-00
Over-Voltage Stall
Prevention
00: Disable over-voltage stall prevention
06-01
Over-Current Stall
Prevention during
Accel
20 to 250% 170
06-02
Over-Current Stall
Prevention during
Operation
20 to 250% 170
00: Disabled
01: Enabled during constant speed operation.
After the over-torque is detected, keep
running until OL1 or OL occurs.
06-03
Over-Torque
Detection Mode
(OL2)
02: Enabled during constant speed operation.
After the over-torque is detected, stop
running.
00