Specifications
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-79
08 - 17
Software Brake Level
(the Action Level of the Brake Resistor)
Unit: 1
Settings 230V series: 370 to 430V Factory Setting: 380
460V series: 740 to 860V Factory Setting: 760
575V series: 925 to 1075V Factory Setting: 950
This parameter sets the DC-bus voltage at which the brake chopper is activated.
This parameter will be invalid for models above 15kW/20hp for which VFDB brake unit must be
used.
08 - 18 Base Block Speed Search
Factory Setting: 00
Settings 00 Speed search starts with last frequency command
01 Speed search starts with minimum output frequency (Pr.01-05)
This parameter determines the AC motor drive restart method after External Base Block is
enabled.
B.B.
A
Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time 08-06
Speed search
Synchronization speed detection
time
Fig. 1: B.B. speed search with last output frequency downward timing chart
FWD Run
Output current
Output voltage(V)
Output frequency
(H)
08-07
Current limit for
speed search