Specifications
Design Guidelines & Procedures Version 18 ©
Electrical Services Section 20.00 / Page 7
Table 2 : Typical Lighting Programs continued
Prog Area Control Operation
G Lecture Theatres and
Auditoriums fitted with
AMX systems
Dimtek - AMX control
panel
Scene Selection as per AMX program.
2 Push Button
‘Dynalite’ panel at
each Entry/Exit - (see
diagram in Appendix A
to this Section)
Top Button (Entry)
Bottom Button (Exit)
Preset 5
Preset 6
8 Push Button/Switch
‘Dynalite’ panel on
teaching wall or
lecturn - (see diagram
in Appendix A to this
Section)
+
At least two
movement detectors
Button 1 - Channels
1,2,4,6,8 (100% IL)
Preset 1
Button 2 – Channels
2,4,6,8 (50% IL)
Preset 2
Button 3 – Channels
2,4,5,6,8 (25% IL)
Preset 3
Button 4 – Channels
5,6,8 (25% IL)
Preset 4
Switch 5 – Channel 1
White board (On/Off)
Switch 6 – Channel 2 FOH lights (On/Off)
Switch 7 – Channel 3
Switch 8 – Channel 4
Spot lights(On/Off)
House lights (On/Off)
H Teaching Rooms e.g.
Seminar Rooms, PBL
Rooms
1 No. one (1) gang
switch panel at entry;
I No. three (3) gang
switch panel at lecturn
or teaching wall.
2 No. (max.)
movement detectors
Single gang switch at entry will activate all lights
in the room.
The three (3) gang switch will individually
control lights at the whiteboard, front of house
or main house lighting.
When the lights are ‘On’ and no movement has
been detected by the PE cell/s for a period of 60
minutes, all fittings will dim to ‘Off’. Detection of
movement by the PE cell/s will return the fittings
to their previous state.
I External Lighting (above
ground level on
building, eg balcony
external walkways etc.)
Detector/s
Single gang switch
Light level and Motion detection. On after dark
in conjunction with movement, time-delay off
nominally of 20 minutes.
Switch shall override detector operation.
J External Lighting (at
ground level or away
from building)
CCMS: Auto/On/Off
switch mounted on DB
Auto = CCMS time schedule control, typically
Dusk till Dawn
K External illuminated
Signage and feature
lighting
CCMS: Auto/On/Off
switch mounted on DB
Auto = CCMS time schedule control, typically
Dusk till nominated hour typically 11pm.
L Plantrooms & service
risers
Local switch ON/OFF
Notes:
Lux levels quoted above are for typical areas and will need to be changed to suit specific task lighting.
Additional control scenarios will need to be developed to suit specific project requirements
e.g. competition and training level lighting on sports facilities or specialist laboratories.