Specifications
Design Guidelines & Procedures Version 18 ©
Electrical Services Section 20.00 / Page 6
The interface between the AMX system and the lighting control system shall be sufficient to
enable switching group control by the AMX via the lighting control system. Interface cabling is
within the Contractor’s scope of works.
The AMX system active equipment will be provided as noted in the SDFs.
20.03.05 Programming of Lighting Controls
The lighting control system shall be commissioned to program all dimmers and electronic ballast
controllers.
Lighting control shall initially be configured as per the following table;
Table 2 : Typical Lighting Programs
Prog Area Control Operation
A Small rooms,
typically offices
a) 1 Gang Switch
Panel:
Position 1 – ‘On’
Position 2 – ‘Off’
b)Movement
detector
Operation to Position 1 will energise lights to 360 lux.
Illuminance level will be detected by the PE cell and
ramp all fittings up or down to achieve the assigned
illuminance level.
When the lights are ‘On’ and the PE cell has detected
no movement for a period of 40 minutes, all fittings will
dim to ‘Off’. Detection of movement will return the
fittings to ‘On’.
B Open Office/ Daylit
areas, General
areas of Learning
Centres
As above As for
A
above
C Foyers, Corridors,
Toilets & Internal
Stairwells
As above As for A above but with 180 lux illumination level and
20 minutes delay time
D Large Storage As above As for A above but with 180 lux illumination level
E Small Storage As above As for
A
above but with 180 lux illumination level
F Video
Conferencing
Room
a) 2 Button
‘Dynalite’ panel
b) Movement
detector
Button 1 = ‘On/Off’ function to provide 360 lux for
general lighting
Button 2 = ‘Off/Off’ function to provide 600 lux vertical
illuminance at 1500mm above f.f.l.
When the lights are ‘On’ and no movement has been
detected by the PE cell for a period of 60 minutes, all
fittings will be dimmed to approximately 30%. After a
further period of 5 minutes, all fittings will dim to ‘Off’.
Activation of the PE or buttons within this 65 minute
period will return the fittings to their previous state.
Illumination levels required in the room will be
determined by LES.