Electrical Services Section 20.00 / Page 11
1 No. in the ceiling space within 300mm of the data projector mounting
1 No. for each computer position
2 No. on the wall adjacent to the control console at 600mm above f.f.l.
Provide a separate power circuit for the AV equipment as for Lecture Theatres.
20.07.09 Video Conferencing Rooms
Provide the following GPOs;
4 No. behind the equipment rack.
4 No. on wall adjacent to control console as previously described in Clause 20.07.08.
1 No. for each monitor (single only required).
1 No. on wall opposite viewing wall.
1 No. on wall behind control console.
20.07.10 Learning Centres
Open Access Computer Area – One (1) GPO per computer, printer or photocopier position plus
other outlets as nominated in the SDF.
Help Desk – One (1) GPO to work station, two (2) GPOs to security cupboard.
Group Study Rooms – Two (2) GPOs per room.
Computer Teaching Rooms – One (1) GPO per computer position plus outlets for the console
and data projector as previously described.
Seminar Rooms – As previously described.
20.07.11 Laboratory & Other Special Equipment
Provide power to laboratory equipment as required by the SDFs including the following;
Glass Washer – A three phase five pin ‘Wilco’ power outlet sized to suit the load of the
dishwasher.
Ice Maker – Power supply in accordance with the manufacturers requirements.
Autoclave – Power supply in accordance with the manufactures requirements.
Sensitive analytical, measuring or monitoring equipment shall be served from a separate power
circuit to the space in which they are installed.
Outlets connected to an emergency power supply source shall be fitted with a red rocker switch
and clearly labelled.
20.07.12 Telecommunications Equipment Room (TER)
All power circuits within the TER shall originate from a dedicated load centre installed within the
TER. The poles within the load centre shall be grouped into two sections, Section A (left) and
Section B (right) Provision shall be made for a 50% spare pole capacity within each Section.
Each Section shall be clearly identified using ‘traffolyte’ type labels as DB.TER.A and DB.TER.B.
The power supply to the load centre shall be directly from the building’s Main Switchboard via a
separate feed and be capable of being maintained if the supply to the rest of the building is
switched off.
Two (2) separate 20A power circuits, one from each Section (A left and B right) and from
matching and corresponding pole positions on the board shall feed each cabinet via overhead
chain suspended pendant outlets complete with locking plug retainer (Clipsal 250V, 20A,
56CSC320 – 3 Round Pins).
The load centre shall be fitted with transient overvoltage protectors as described later in this
Section.