Specifications

Design Guidelines & Procedures Version 18 ©
Electrical Services Section 20.00 / Page 10
20.07.02 Access Control
Two (2) dual 10A socket outlets shall be installed for the Security Access Control Equipment on a
dedicated circuit and be located in a service riser or dedicated cupboard as determined by the
CLF Property Services Manager.
20.07.03 Cleaners GPOs
Provide a single GPO, for cleaner’s use at each 20m along all corridors, within each laboratory,
seminar room, auditorium, lecture theatre and the like, at main stair landings and in any room
preceding a room that is not accessed from the before mentioned rooms, excluding cupboards
and minor storerooms.
A GPO shall be provided outside Toilets and each Telecommunications Equipment Room (TER)
adjacent to the entry.
These GPO’s shall have a green rocker and white face plate, be mounted 300mm above finished
floor level and shall be on a dedicated cleaner’s circuit protected by a RCD. Multiple cleaner’s
outlets may co-exist on the same circuit.
20.07.04 Kitchenettes & Tea Preparation
Provide separate circuits for percolators and microwaves, and separate services for dishwashers
and chilled/boiling water units.
20.07.05 Vending Machines
In locations nominated for vending machines, provide a minimum of two (2) GPOs.
20.07.06 Water Heater and Circulating Pump
Water heaters and circulating pumps shall be controlled by CCMS with over-riding control at the
distribution board supplying the circuits. A water heater is any appliance that raises the
temperature of water above ambient.
20.07.07 Lecture Theatres
Provide GPOs etc in accordance with the following;
Bio Box - Four (4) GPOs shall be provided for additional equipment and general use where a
Bio Box is provided.
Front of Theatre (FOH) – One (1) GPO shall be provided on each side of the front wall. Two (2)
GPOs shall be located on the stair riser under the first row of seats.
Side Walls of Lecture Theatre – This requirement is deleted.
Seating Area in Lecture Theatre – Provide one (1) Double GPO for every 20 seats in the
Theatre. If the seat is fixed, then the DGPOs shall be floor mounted just behind the line of the
seat front edge and below an arm rest. If the seats are the tilt-up type, then the DGPOs shall be
mounted on the back face of the chair support rails.
Lectern - Four (4) GPOs shall be provided within the lectern for audio visual equipment. Two (2)
additional GPOs shall be provided on the lectern wing adjacent to the AMX touch panel.
Power for Audio Visual Equipment - Each Theatre fitted with AV equipment shall be provided
with a separate power circuit to service the equipment which includes the projector.
20.07.08 Seminar Rooms, Computer Teaching & Other Specialist Teaching Spaces
Provide double GPOs in accordance with the following;
1 No. on the front wall, one each side.
1 No. on the rear wall