Specifications

150972 A-1
Appendix A
Compatible Devices
A.1 Two-Wire Smoke Detectors
The table below lists two-wire smoke detectors that are compatible with the IntelliKnight fire
control panel. The table is organized by manufacturer. The columns show the number of
detectors per loop that can be used.
Table A-1: Compatible Two-Wire Smoke Detectors
Manufacturer
Model Name or Number
(Base model name or number in
parentheses.)
Compatibility ID
# per Loop
Head Base
Apollo
55000-350 (45681-200) 55000-350 45681-200 24 / loop
55000-250 (45681-200) 55000-250 45681-200 24 / loop
Detection Systems
DS250 (MB2W or MB2WL) B A 18 / loop
DS250HD (MB2W or MB2WL) B A 18 / loop
DS250TH (MB2W or MB2WL) B A 18 / loop
ESL
429C (S10A) N/A S10A 30 / loop
429CRT (S11A) N/A S11A 30 / loop
429CST (S11A) N/A S11A 30 / loop
429CT (S10A) N/A S10A 30 / loop
609U01-11 S10 S00 40 / loop
609U02-11 S10 S00/S03 40 / loop
611U (601U or 602U) S10 S00/S03 40 / loop
611UD (601U or 602U) S10 S00/S03 40 / loop
611UT (601U or 602U) S10 S00/S03 40 / loop
612U (601U or 602U) S10 S00/S03 40 / loop
612UD (601U or 602U) S10 S00/S03 40 / loop
711U (701E or 701U) N/A S10A 25 / loop
712U (701E or 701U) N/A S10A 25 / loop
713-5U (702E or 701U) N/A S10A 25 / loop
713-6U (702E or 701U) N/A S10A 25 / loop
721-U (S10A) N/A S10A 30 / loop
721-UT (S10A) N/A S10A 30 / loop
Falcon
525 FDT1 N/A 17 / loop
525T FDT1 N/A 17 / loop