Specifications
Testing and Troubleshooting
150972 10-3
10.3 Built-in Troubleshooting and Testing Tools
The IntelliKnight fire control panel has several built-in testing and troubleshooting tools that
can be utilized to save time while testing and troubleshooting points and SLC devices.
10.3.1 SLC Device Locator
SLC device locator can be used to locate a device on a SLC loop.
Follow these steps to locate a particular SLC device:
1. Select (Point Functions) from the Installer Menu.
2. Select (SLC Dev Locator).
A message similar to the one shown in Figure 10-1 will display.
Figure 10-1 Shut Down Warning
3. Press the or arrow to toggle 12 to <(6then press .
If 12 is chosen you will exit back to the Point Function menu.
If <HV is chosen the system will cease normal operation leaving the premise unprotected.
4. Select the SLC loop.
5. Enter the SLC address of the device you wish to locate.
The LED on the selected device will start flashing.
6. Press any key to exit SLC device locator function.
Note: Once you exit the system will resume normal operation.
2
4