Specifications

Reporting
150972 9-5
Zone-based AUX 1 switch input has been re-
enabled.
Disable 3 571 Exp ID Pnt #
Zone-based AUX 2 switch input has been re-
enabled.
Disable 3 571 Exp ID Pnt #
Positive alarm sequence acknowledge switch has
been re-enabled.
Disable 3 571 Exp ID Pnt #
A detection acknowledge switch has been re-
enabled.
Disable 3 571 Exp ID Pnt #
A fire drill switch has been re-enabled. Disable 3 571 Exp ID Pnt #
A silence switch has been re-enabled. Disable 3 571 Exp ID Pnt #
A reset switch has been re-enabled Disable 3 571 Exp ID Pnt #
A system-based AUX 1 switch input has been re-
enabled.
Disable 3 571 Exp ID Pnt #
A system-based AUX 2 switch input has been re-
enabled.
Disable 3 571 Exp ID Pnt #
A constant on auxiliary power output has been re-
enabled.
Disable 3 571 Exp ID Pnt #
A resettable auxiliary power output has been re-
enabled.
Disable 3 571 Exp ID Pnt #
A door holder auxiliary power output has been re-
enabled.
Disable 3 571 Exp ID Pnt #
User has initiated dialer test. Test 1 601 00 Channel #
Periodic test event. Test 1 602 00 Channel #
Fire drill has begun. Test 1 604 00 000
Fire drill has ended. Test 3 604 00 000
Walk test begin. Test 1 607 00 000
Walk test end. Test 3 607 00 000
SLC address programming started; system has
been shut down.
Test 1 607
SLC address programming ended; system has been
re-enabled.
Test 3 607
Panel date has been changed. Trouble 1 625 00 000
Panel time has been changed. Trouble 1 625 00 000
Local programming begin. Trouble 1 627 00 000
Remote programming begin. Trouble 1 627 00 000
Local programming ended normally. Trouble 1 628 00 000
Local programming aborted or ended with errors. Trouble 1 628 00 000
Table 9-2: Ademco Contact ID Output
Event Description Event Family
Event
Qualifier
1=New,
3= Restore
Event Code Group #
Zone /